Schneider C11N6TM016L | circuit breaker ComPacT NSXm N (50 kA at 415 VAC), 4P 3d, 16 A rating TMD trip unit, EverLink connectors
1. Technical Specifications C11N6TM016L
-
Product Reference: C11N6TM016L
-
Series: ComPacT NSXm
-
Type: Molded Case Circuit Breaker (MCCB)
-
Poles: 4P (3d)
-
3 poles protected (phases), 1 pole dedicated neutral (not protected)
-
-
Rated Current (In): 16 A
-
Trip Unit Type:
-
TMD (Thermal Magnetic Device)
-
Fixed settings for thermal and magnetic trip curves
-
-
Breaking Capacity:
-
Icu = 50 kA at 415 V AC (IEC 60947-2)
-
-
Rated Operating Voltage (Ue):
-
220–415 V AC (50/60 Hz)
-
-
Rated Insulation Voltage (Ui): 800 V
-
Rated Impulse Withstand Voltage (Uimp): 8 kV
-
Utilization Category: A (non-selective)
-
Connection Type:
-
EverLink™ patented terminals for reliable, vibration-proof connections
-
Suitable for flexible, rigid, or ferruled cables
-
-
Mounting Type:
-
Fixed, DIN rail or backplate mounting
-
-
Conformity & Standards:
-
IEC 60947-2
-
CE, RoHS compliant
-
-
Dimensions:
-
Compact frame size (NSXm body): approx. 90 mm wide
-
-
Degree of Protection:
-
IP40 (front face), IP20 (terminals)
-
2. Key Features
-
Compact footprint with 4-pole protection for small-scale and space-constrained panels
-
High short-circuit breaking capacity (50 kA) ensures strong protection for critical circuits
-
Thermal-magnetic trip unit provides dual protection:
-
Thermal: Overload (long-time protection)
-
Magnetic: Short-circuit (instantaneous protection)
-
-
EverLink™ terminal technology:
-
Prevents loosening over time due to thermal cycling or vibrations
-
Maintains reliable torque and cable clamping
-
-
Integrated neutral simplifies wiring and improves safety in 3-phase + N applications
-
Padlockable toggle and compatibility with auxiliary accessories (OF/SD contacts, shunt trip, etc.)
-
Designed for panel integration, offering a clean and modular assembly
-
Fully tested under international standards for safety, performance, and endurance
3. Applications
-
Industrial control panels requiring reliable short-circuit and overload protection
-
Commercial distribution boards where space-saving and 4P protection are needed
-
Final distribution in 3-phase + N low-voltage systems (up to 415 V AC)
-
Ideal for protecting:
-
Small motors
-
HVAC systems
-
UPS outputs
-
Lighting circuits
-
Distribution to sub-panels or field equipment
-
-
Suitable for:
-
Data centers
-
Building automation systems
-
Renewable energy panels
-
Machine control cabinets
-
-
Frequently used in harsh environments where EverLink’s anti-vibration benefit is key (e.g., compressors, elevators, pumps)


Reviews